Analisis Daya Listrik Total Harmonic Distortion Terhadap Efisiensi Energi di PT. Indonesia Chemical Alumina
DOI:
https://doi.org/10.63440/jef.v3i1.127Keywords:
THD, Power Quality, Energy Efficiency, Power FactorAbstract
This study analyzes the relationship between Total Harmonic Distortion (THD) and electrical energy efficiency in medium-voltage distribution panels at PT Indonesia Chemical Alumina. Measurements were conducted using the ABB ANR96 power analyzer connected via RS485 communication and monitored using ABB SW01-128 software for seven days. The observed parameters include THDv, THDi, power factor (PF), and kW/kVA ratio. The results show that the average THDv in all panels is 0%, indicating voltage distortion within standard limits. THDi values vary across panels, with the highest value recorded at 3.60% and the lowest at 0%. The average PF ranges from 0.66 to 0.72, indicating moderate efficiency conditions. Correlation analysis shows a negative relationship between THDi and energy efficiency with a correlation coefficient of −0.2329 and a determination coefficient of 24.73%, categorized as low correlation. These findings indicate that although THDi values are relatively small, they still directly influence energy efficiency in medium-voltage distribution systems.
Downloads
References
[1] J. Zheng, R. Chen, Z. Zhang, X. Wei, and J. Xue, “Analysis and comprehensive assessment method of power quality in advanced distribution networks based on complex network theory,” Front. Energy Res., vol. 12, no. December, pp. 1–13, 2024, doi: https://doi.org/10.3389/fenrg.2024.1501006
[2] G. N. Popa, “Electric Power Quality through Analysis and Experiment,” Energies, vol. 15, no. 21, 2022, doi: https://doi.org/10.3390/en15217947
[3] M. Al Saaideh, O. Ananbeh, T. Almomani, E. A. Feilat, and H. J. Khasawneh, “Power quality audit of a school of engineering building - case study,” Int. J. Emerg. Trends Eng. Res., vol. 8, no. 1, pp. 151–156, 2020, doi: https://doi.org/10.30534/ijeter/2020/20812020
[4] M. C. G. Ramos and C. M. V. Tahan, “An assessment of the electric power quality and electrical installation impacts on medical electrical equipment operations at health care facilities,” Am. J. Appl. Sci., vol. 6, no. 4, pp. 638–645, 2009, doi: https://doi.org/10.3844/ajas.2009.638.645
[5] K. Olikara, “Power Quality Issues, Impacts, and Mitigation for Industrial Customers,” Power-Wp002a-En-P, p. 8, 2015. http://www.southwoodient.com/
[6] T. Siostrzonek, J. Wójcik, M. Dutka, and W. Siostrzonek, “Impact of Power Quality on the Efficiency of the Mining Process,” Energies, vol. 17, no. 22, pp. 1–14, 2024, doi: https://doi.org/10.3390/en17225675
[7] Koerniawan Tony and Hasanah Aas Wasri, “Kajian Harmonisa Pada Pemakaian Tenaga Listrik Gedung STT PLN Jakarta,” Kilat, vol. 8, no. 2, pp. 180–189, 2019.
[8] R. Irwanto, “Analisa Harmonisa Pada Transformator 3 Fasa,” J. Persegi Bulat, vol. 1, no. 1, pp. 7–12, 2022, doi: https://doi.org/10.36490/jurnalpersegibulat.v1i1.248
[9] F. J. Siahaan, E. M. Silalahi, B. Widodo, and R. Purba, “Pengukuran Total Harmonic Distortion (Thd) Terhadap Lampu Hemat Energi (Lhe) Dan Light-Emitting Diode (Led),” Lektrokom J. Ilm. Tek. Elektro, vol. 3, no. 1, p. 8, 2020, doi: https://doi.org/10.33541/lektrokom.v3i1.3372
[10] S. Thakur, N. M. Butlero, and J. Holboll, “Effects of harmonics on temperature rise and power loss of a distribution transformer,” 2022 9th Int. Conf. Cond. Monit. Diagnosis, C. 2022, vol. 2022-Janua, pp. 732–735, 2022, doi: https://doi.org/10.23919/CMD54214.2022.9991585
[11] E. ScienceDirect, “Total Harmonic Distortion On this page Chapters and Articles Interfacing DACs to Loads Assessment and mathematical modeling of energy quality parameters of grid connected photovoltaic inverters.” [Online]. Available: https://www.sciencedirect.com/topics/engineering/total-harmonic-distortion
[12] M. S. Seddik, M. B. Eteiba, and J. Shazly, “Evaluating the Harmonic Effects on the Thermal Performance of a Power Transformer,” Energies, vol. 17, no. 19, 2024, doi: https://doi.org/10.3390/en17194871
[13] D. B. M. Said, Z. I. M. Yassin, N. Ahmad, N. N. B. N. Abd Malik, and H. Abdullah, “Impact of unbalanced harmonic loads towards winding temperature rise using fem modeling,” Indones. J. Electr. Eng. Informatics, vol. 8, no. 2, pp. 409–418, 2020, doi: https://doi.org/10.11591/ijeei.v8i2.1283
[14] N. R. Tinambunan and Rahmaniar, “Analisis Dampak Harmonisa terhadap Efisiensi Energi pada Pengoperasian Inverter Air Conditioner,” Jurnal Nasional Teknologi Komputer, vol. 5, pp. 148–159, 2025. doi https://doi.org/10.61306/jnastek.v5i3.200
[15] Firoz Kobir, Abdur Razzak Khan, and Vinukumar Luckose, “Harmonic distortion-based condition monitoring of distribution transformers in a solar farm,” World J. Adv. Res. Rev., vol. 26, no. 2, pp. 3427–3435, 2025, doi: https://doi.org/10.30574/wjarr.2025.26.2.2009
[16] M. Kumar, M. A. Uqaili, Z. A. Memon, and B. Das, “Experimental Harmonics Analysis of UPS (Uninterrupted Power Supply) System and Mitigation Using Single-Phase Half-Bridge HAPF (Hybrid Active Power Filter) Based on Novel Fuzzy Logic Current Controller (FLCC) for Reference Current Extraction (RCE),” Adv. Fuzzy Syst., vol. 2022, 2022, doi: https://doi.org/10.1155/2022/5466268
[17] G. Davide, “Harmonic Distortion Models of Non-Linear Loads,” Eindhoven University of Technology, 2006. [Online]. Available: https://research.tue.nl/files/68270318/615682.pdf
[18] P. R. Nasini, N. R. Narra, and A. Santosh, “Modeling and Harmonic Analysis of Domestic/Industrial Loads,” Int. J. Eng. Res. Appl., vol. 2, no. 5, pp. 485–491, 2012.
[19] A. M. AKBAR and C. F. NUGRAHA, “Analisis Harmonik dan Perbaikan Nilai THD Arus dengan Perancangan Filter Pasif Single-Tuned,” ELKOMIKA J. Tek. Energi Elektr. Tek. Telekomun. Tek. Elektron., vol. 12, no. 4, p. 892, 2024, doi: https://doi.org/10.26760/elkomika.v12i4.892
[20] L. Assaffat and S. A. Chandra, “Analisis Perbaikan Thd Tegangan Listrik Dengan Filter Pasif Studi Kasus Di Finish Mill Tuban IV PT Semen Indonesia (Persero) Tbk,” RELE (Rekayasa Elektr. dan Energi) J. Tek. Elektro, vol. 1, no. 1, pp. 37–43, 2018, doi: https://doi.org/10.30596/rele.v1i1.2272
[21] O. A. Rozak, “Simulasi Perbaikan THD pada Sistem Distribusi Listrik dengan Filter Harmonisa Berbasis Software ETAP 12.6.0,” Epic J. Electr. Power, Instrum. Control, vol. 2, no. 2, pp. 1–12, 2019, doi: https://doi.org/10.32493/epic.v2i2.2878
[22] K. G. H. Mangunkusumo, J. Hartono, and P. A. A. Pramana, “Harmonic evaluation of Plug-in Electric Vehicle on distribution network system,” IOP Conf. Ser. Mater. Sci. Eng., vol. 1098, no. 4, p. 042034, 2021, doi: https://doi.org/10.1088/1757-899x/1098/4/042034
[23] A. Zulkarnaini, R. Sinambela, L. Lisapaly, and M. Manik, “Analisis Pengukuran Harmonisa Tegangan Dan Arus Listrik Di Gedung Administrasi Universitas Jayabaya,” Transm. J. Ilm. Tek. Elektro, vol. 26, no. 3, pp. 132–138, 2024, doi: https://doi.org/10.14710/transmisi.26.3.132-138
Downloads
Published
Issue
Section
License
Copyright (c) 2026 Hisyam Abdullah, Adi Mulyadi, Ratna Mustika Yasi (Author)

This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.